DSpace Repository

Effect of titanium oxide on dissipation factor for the insulation of transformer oil [articol]

Show simple item record

dc.contributor.author Dessouky, Sobhy. S.
dc.contributor.author Abdelwahab, Saad A.Mohamed
dc.date.accessioned 2024-02-05T12:37:47Z
dc.date.available 2024-02-05T12:37:47Z
dc.date.issued 2021
dc.identifier.citation Dessouky, Sobhy; Abdelwahab,Saad A.Mohamed. Effect of titanium oxide on dissipation factor for the insulation of transformer oil. Timişoara: Editura Politehnica, 2021 Disponibil la https://doi.org/10.59168/OCBI7815 en_US
dc.identifier.uri https://dspace.upt.ro/xmlui/handle/123456789/6171
dc.identifier.uri https://search.crossref.org/search/works?q=10.59168%2FOCBI7815&from_ui=yes Link DOI
dc.description.abstract In most cases, The electrical insulation of the transformer oil is exposed to different internal problems, such as short circuit , over voltage, over load, over excitation and etcetera. The insulation of transformer is sever decreased into minimum value, that is unacceptable. This requires some treatments of oil liquid ,such as refining or replacing the old oil, which is a very expensive process. In this paper, The old oil is enhanced with nanoparticles (NPs) for reusing in the power transformer again. The NPs enhance the insulation, physical and chemical properties of transformer oil. The breakdown voltage(BDV) and the dissipation factor (DF) are tested for old oil and after addition the NPs according to IEC standard methods. The NPs are many types, Titanium oxide (TiO2) is one of them, which is used in this research. NPs reduce the effect of moisture as it absorb and form hydroxyl groups around. Also, reduce the effect of dissolved carbonate in oil without harmful effects. A comparative study is conducted to identify the effects of using NPs in transformer oil to ensure their effect on electrical insulation, Also to be used again. The results show that adding small amount of TiO2 to transformer oil improves its breakdown strength as well as dissipation factor. en_US
dc.language.iso en en_US
dc.publisher Timișoara: Editura Politehnica en_US
dc.relation.ispartofseries Journal of Electrical Engineering;Vol 21 No 3
dc.subject Nanoparticles en_US
dc.subject Dissipation factor test en_US
dc.subject Breakdown voltage test en_US
dc.subject Titanium oxide en_US
dc.title Effect of titanium oxide on dissipation factor for the insulation of transformer oil [articol] en_US
dc.type Article en_US