DSpace Repository

SFRA ability in detection of Deformation in Transformers Windings: A field experience of 400kV 167MVA single phase unit [articol]

Show simple item record

dc.contributor.author Chavda, Ashok
dc.contributor.author Pandya, Vivek
dc.date.accessioned 2024-06-04T09:52:46Z
dc.date.available 2024-06-04T09:52:46Z
dc.date.issued 2021
dc.identifier.citation Chavda, Ashok; Pandya, Vivek. SFRA ability in detection of Deformation in Transformers Windings: A field experience of 400kV 167MVA single phase unit. Timişoara: Editura Politehnica, 2021. en_US
dc.identifier.issn 1582-4594
dc.identifier.uri https://dspace.upt.ro/xmlui/handle/123456789/6285
dc.description.abstract Sweep Frequency Response Analysis has become very popular now – a - days due to its ability to provid e comprehensive information regarding mechanical as well as electrical condition of power transformers. The SFRA is a comparative method and provides better information when evaluation of Transformer condition is done by comparing actual set of SFRA result s with reference results. This field experience consists 400/220/33KV ICT bank, formed with three single phase unit with capacity of 167MVA each. A heavy fault current was fed by ICT due to failure of LA provided on delta winding formed outside. Mechanical defects ostensibly occur due to a short circuit current flowing through power transformer in case of terminal faults i.e. fault near to power transformer. To know the mechanical integrity of power transformer SFRA test is carried out and is supported by o ther tests i.e. DC resistance, Magnetic balance, Winding resistance, capacitance and tan delta etc. The test results reveals that SFRA is capable of providing more information about mechanical deformation about power transformers compared to other tests. en_US
dc.language.iso en en_US
dc.publisher Timișoara : Editura Politehnica en_US
dc.relation.ispartofseries Journal of Electrical Engineering;Vol 21 No 2
dc.subject Sweep Frequency Response Analysis en_US
dc.subject Winding Deformation en_US
dc.subject Inter-connected Transformer ICT en_US
dc.title SFRA ability in detection of Deformation in Transformers Windings: A field experience of 400kV 167MVA single phase unit [articol] en_US
dc.type Article en_US