Abstract:
High Voltage (HV) increased safety (Ex e) motors
are being designed for safe operation in the hazardous area.
The motor time tE for increased safety motor is prime safety
parameter. The higher value of time tE means insulating
system of Ex e motor is able to withstand the locked condition
for long time so motor will be more safe for long duration
during in abnormal condition in hazardous area. The
research work shows that the time tE of Ex e motor can be
increased by increasing the mass of rotor bar or by
increasing the stator coil pitch. Low speed and a high speed
HV Ex e motor were selected to redesign with increasing
rotor bar mass and stator coil pitch. The time tE and other
parameters of redesigned motors have been compared with
standard design of Ex e motor. It is anticipated that this study
will be of immense benefit to Ex e HV motor designers.