Abstract:
This paper presents Pseudo-Derivative
Feedback with Feed-forward controller (PDFF)
controller based Automatic Generation Control (AGC) of
a two area interconnected power system. The control
parameter of PDFF controller are optimized employing
Flower Pollination Algorithm (FPA) in order to achieve
the optimal transient response of the test system under for
different types of possible transactions in restructured
environment. The proposed PDFF controller are used in
AGC application which locates the zero at an optimal
place that shortens the step response rise time without
overshoot and gives better dynamic performance of the
system over PI controller. Integral Square Error (ISE)
criterion of the test system was considered as an objective
function to be minimized for tuning the gains of PDFF
controller using FPA. In this study two type of test system
is considered such as two area Hydro-Thermal and
Thermal-Diesel power system. The simulation results
show that the proposed FPA tuned PDFF controller
improves the dynamic response of the restructured power
system. The convergence speed performance of the
proposed FPA algorithm is significantly better compared
to those achieved by the existing algorithms. Moreover
the Power System Restoration Indices (PSRI) is computed based on system dynamic performances and the remedial
measures to be taken can be adjudged. These PSRI
indicates that the ancillary service requirement to
improve the efficiency of the physical operation of the
power system with the increased transmission capacity in
the network.